Main page content
UEi C155 Combustion Analyzer Review: Specs, Field Notes, and Modern Replacement
Production Status: Discontinued by Manufacturer.
Direct Replacement: UEi C165+ Residential and Commercial Combustion Analyzer. The newer model adds a 10,000 ppm H2-compensated CO sensor, NOx filtration, wireless pipe clamp integration, a 6-line display, and mobile app reporting.
Jobsite Verdict and Historical Context
The UEi C155, sold as the Eagle X Xtended Life Combustion Analyzer, served residential and light commercial HVAC technicians as a rugged rotary-dial instrument. Its defining feature was an Electro-Optical Sensor that measured CO2 directly and calculated O2 mathematically instead of using a short-lived electrochemical O2 cell.
In daily service work, that design eliminated annual oxygen sensor replacements and lowered long-term ownership costs. However, its 2,000 ppm standard CO ceiling, lack of wireless probe integration, and retired factory warranty support eventually led UEi to replace this platform. UEi replaced the C155 lineup with the modern C160 and C165+ series.
Quick-Lookup Technical Specifications
| Specification | UEi C155 Rating |
|---|---|
| Direct Gas Measurements | CO: 0 to 2,000 ppm (4,000 ppm max for 15 min); CO2: 0 to 20% via EOS sensor |
| Calculated Parameters | O2 (0 to 21%), Gross/Net Efficiency (0 to 99.9%), Excess Air (0 to 250%), CO Air-Free, CO/CO2 Ratio |
| Flue and Inlet Temperature | 20°F to 2,400°F (-29°C to 1,315°C) via K-type probe; Ambient Inlet: 32°F to 112°F (0°C to 50°C) |
| Differential Pressure | ±0.08 in. wc (0.001 in. wc resolution), ±0.4 in. wc, and ±32 in. wc ranges |
| Display and Memory | 4-line backlit LCD (early units used 2-line), 179 memory positions, IR printer port |
| Power and Weight | 4 AA alkaline batteries (approx. 12-hour runtime), 2.2 lbs with protective magnetic boot |
| Pre-Programmed Fuels | Natural Gas, Propane, Butane, LPG, Light Oil, Heavy Oil, Bio-Fuel, and Wood |
Field Ownership and Maintenance Notes
Technicians still running a working UEi C155 on service calls should keep these maintenance details in mind:
- Filters and Water Trap Parts: The analyzer uses UEi 17631 inline particle filters, the SM11827 water trap assembly, and CM11667/2 drain plugs.
- Probes and Thermocouples: Factory kits shipped with the KMCP2 12-inch stainless steel flue probe, ATT29 K-type temperature probes, and the SM11103 inlet tube connector.
- CO Sensor Saturation Limits: Although the EOS CO2 sensor carried a 10-year life expectancy, the electrochemical CO cell saturates quickly above 2,000 ppm. Pull the probe and purge with fresh air immediately if readings spike on a fouled heat exchanger.
- Condensate Protection: Drain the rear water trap after testing high-efficiency condensing furnaces or boilers, and replace damp 17631 filters before zeroing the pump.
- Calibration Support: Factory warranty coverage for the C155 chassis has ended, but independent NIST-traceable calibration labs can still verify and adjust working units.
Modern Replacement: UEi C165+
If your C155 has failed calibration or needs replacement, the UEi C165+ is the direct current-generation successor. It upgrades the older Eagle X design in three key jobsite areas:
- Higher CO Range and Sensor Protection: Expands CO measurement to 10,000 ppm with hydrogen compensation, an integrated NOx filter, low-flow detection, and an automatic purge pump.
- Wireless Probes and App Reporting: Links directly to UEi WPC2 wireless pipe clamp probes and sends test reports to mobile devices without an infrared printer.
- Expanded Display and Warranty: Adds a 6-line backlit screen, a Heat Exchanger Test, 30-second startup, rechargeable batteries, and up to a 10-year warranty.
Technician FAQ
Is the UEi C155 combustion analyzer still in production?
No. UEi discontinued the C155 analyzer along with the C155KIT, C155BTKIT, and C155OILKIT bundles.
What replaced the UEi C155?
The UEi C165+ is the direct modern equivalent. It offers a 10,000 ppm H2-compensated CO sensor, wireless pipe clamp connectivity, mobile app reporting, and a 6-line display.
What replacement consumables still fit the UEi C155?
Working units still accept UEi 17631 particulate filters, SM11827 water traps, CM11667/2 drain plugs, and standard ATT29 K-type thermocouple probes.